The Problem

 

uRisk were contacted to help determine the cause of Legionella Positive results at medical centre. Our specialists were promptly booked in and dispatched to the GP surgery to assess the route cause of Legionella growth.

s

Our Findings

 

uRisk quickly carried out a full legionella risk assessment and sampling plan to determine the high risk areas that encouraged the growth. The breeding area was identified as a TMV installed on the flow immediately downstream of the hot water cylinder. This meant that whilst the hot water cylinder was set to 60-65°C to reduce the risk from legionella growth, the TMV reduced the hot water pipework immediately to 41°C, to then distribute at this temperature around the entire hot water system. This created Legionella positive results of 3,500 CFU/mL.

As per the HSG 274 Part 2 legionella guidelines for hot and cold systems, TMVs should be installed within 2m of each water outlet (tap) to keep the hot water distribution above 50°C (55°C in healthcare). In this case, the only TMV present was well over the 2m from each outlet as it was situated on the cylinder. The TMV needed to be removed from the cylinder flow so that hot water could distributed around the hot water pipework at 55-60°C. With the hot water only being reduced to 41°C locally under each outlet. This would help to discourage legionella from growing, whilst also protecting users from scalding temperatures.

Customer Success Stories

Large Project of 160 Coffee Shops

Large Project of 160 Coffee Shops

Customer: Coffee Chain     Location: England and Wales, Scotland, and IrelandThe Problem   uRisk were contacted to help to provide legionella risk assessments, legionella sampling, legionella remedial works, legionella training, and legionella monitoring to a...

read more
Reducing Fear and Panic from Legionella

Reducing Fear and Panic from Legionella

Customer: Dental Practice     Location: West MidlandsThe Problem   uRisk had been contacted by a dental practice with 5 premises. The practice had recently purchased online legionella DIY testing kits which returned positive 3 out of the 5. The sampling company...

read more
Working with Charities

Working with Charities

Customer: Nationwide Charity     Location: England and Wales, ScotlandThe Problem   uRisk were approached by a nationwide charity to provide legionella sampling across their entire store portfolio based on their legionella risk assessments from a third party.Our...

read more

We want to help you comply!